Commands Reference
CoolMaster PRM
14
www.xdimax.com
© 2009 XDIMAX LTD
Rev 3.0
EXAMPLE
>stat2
100 ON 12C 12,41C High Cool OK 0
101 OFF 32C 04,93C Low Dry OK 1
102 ON 07C 08,27C High Dry OK 0
103 OFF 01C 26,84C Med Dry OK 0
104 ON 04C 24,08C High Dry OK 0
105 OFF 11C 07,23C Low Dry OK 0
106 ON 11C 14,91C Auto Dry OK 0
107 ON 27C 12,94C Med Cool OK 1
OK
>stat2 101
101 OFF 32C 04,93C Low Dry OK 0
OK
RESPONSE
Position in String
Example
Format
Description
0-2
109
NNN
Indoor unit Centralized Address
4-6
ON
ON or OFF
On/Off Status
8-10
23C
NNC
Set Temperature ºC
12-17
24,08C
NN,NNC
Room Temperature ºC
20-23
Auto
Low or Med or High or Auto
Fan Speed
25-28
Cool
Cool or Heat or Fan or Dry
Operation Mode
30-32
OK
OK or XN
OK or Failure code
34
0
0 or 1
Filter Reset Sign present
EXIT CODE
OK
Request Successfully Executed
ERROR:1
Unit with specified UID not found
COMPATIBILITY
CoolMaster 1000D
v 0.3.1
CoolMaster 2000S
v 2.0.9
3.1.16 stat3
SYNOPSIS
stat3 [UID]
DESCRIPTION
Get Indoor unit(s) status. Specific indoor unit can be addressed by UID. If no UID provided in request,
response will contain information about all units. stat3 compared to stat2 has no fractional part in the
room temperature presentation.
EXAMPLE
>stat3
100 ON 12C 12C High Cool OK 0
101 OFF 32C 04C Low Dry OK 1
102 ON 07C 08C High Dry OK 0
103 OFF 01C 26C Med Dry OK 0
104 ON 04C 24C High Dry OK 0
Vue de la page 13