Vue de la page 11
Commands Reference
CoolMaster PRM
12
www.xdimax.com
© 2009 XDIMAX LTD
Rev 3.0
version
Read
Firmware Version
echo
R/W
0-Disable 1-Enable Commands echo
lcd
R/W
LCD size
simul
R/W
Number of Indoor units permanently simulated. If simul is not zero
CoolMaster will simulate given number of units after reset.
CS count
Read
Check Sum errors counter
TO count
Read
Timeout errors counter
EXAMPLE
S/N : 0041
myid : 0A
version : 2.1.4
echo : 1
lcd : 8
simul : 0
CS count: 0
TO count: 0
OK
Query configuration
>set echo 0
OK
Set echo option (disable echo)
EXIT CODE
OK
Request Successfully Executed
COMPATIBILITY
CoolMaster 1000D
v 0.3.0
CoolMaster 2000S
v 2.0.9
3.1.13 simul
SYNOPSIS
simul <N>
DESCRIPTION
Simulate N indoor units. Simulation mode can be used to debug Home Automation Controller software
without connecting CoolMaster to Air Conditioning system line. To exit simulation mode set N to zero or
restart CoolMaster.
EXAMPLE
>simul 20
OK
Simulate 20 Indoor Units
>simul 0
OK
Terminate simulation mode
EXIT CODE
OK
Request Successfully Executed
COMPATIBILITY
CoolMaster 1000D
v 0.3.0