Connecting 9000 Series Sensors to Monitors
Entek 9000 Series Sensor Installation Guide 19
CONNECTING 9000 SERIES SENSORS
TO XM-120/121/122 VIBRATION MODULE CHANNEL 1
Shield Ground
Pin A - Signal
Pin B - Common
Cable shield not
connected at this end
0
16
22
6
21
Channel 1 Input Signal
Signal Common
5
37
Jumping terminals
5 to 6 & 21 to 22
configure the
transducer power
supply for IEPE
tranducer(s)
Note: You may ground the cable shield at either end of the cable. Do not ground the shield
at both ends. Recommended practice is to ground the cable shield at the XM terminal base
and not the sensor.
Note: The internal transducer power supply is providing power to the 9000 sensor.